You are under Home : Products : Ammonia Absorption : Key Features Previous : Comparisons Next : InstallationsEase of OperationWhere the economy and flexibility is the primary requirement, our units can be controlled by a single operator with simple manual operation. Operators are quick to draw a parallel with ammonia compressor systems, and adapt easily to absorption systems. In larger plants, operation is automatic with three control loops.
Flexible load / temperature operationLike compressor units, Ammonia absorption units can be turned down on load for lower evaporator temperatures. But the comparison ends here. Unlike compressors, AAR units can compensate for fluctuations in cooling water temperature and load fluctuations, simply by increasing the heat supplied. For example; take a unit designed for 20TR, -5oC, 130oC steam, 32oC cooling water. An load of 25TR will drop the temperature to about 0oC, in both compressor and absorption units, other conditions being the same. But lifting the steam temperature to about 140oC would restore -5oC, at 25TR load. This flexibility is not available with compressors. Characteristic features of Guha AAR Systems
|